The interface serves for the establishment of a bidirectional connection between a PC and the installation bus EIB/KNX. The USB connection is separated in a galvanic manner from the EIB/KNX bus. The interface is compatible with ETS (Engineering Tool Software) starting at ETS3 and is also supported by countless visualization programs.
Technical data:
Electrical safety:
- Protection type (according to EN 60529): IP 20
- Safety low voltage SELV DC 24 V
EMC requirements:
- Fulfills EN 61000-6-2, EN 61000-6-3 and EN 50090-2-2
Environmental conditions:
- Environment temperature during operation: - 5 ... + 45 °C
- Storage temperature: - 25 ... + 70 °C
- Rel. humidity (not condensation): 5 % … 93 %
Approval:
- EIB / KNX
Mechanical data:
- Casing: Plastic
- Series installation, installation width 2 TE
- Weight: about 100 g
- Fire load: about 1000 kJ
Power input: < 300 mW
Connections: EIB/KNX-connection clamps
USB-interface: USB connector type B,
Line length max. 5 m;
Display elements
- Display-LED (green) for USB-connection
- Display-LED (yellow) for communication
Power supply
- The switch part for communication through USB is powered by the connected PC/laptop, the power supply is displayed by the green LED.
Power input: < 200 mW
- The switch part for communication through EIB/KNX is powered by the connected EIB/KNX bus.